PRODUCT
LAN connection type IO controller
LA-5R(G)
● LAN interface: 10Base-T/100Base-TX.
● One to Multiple TCP connection.
● With an input unit (LA-5P-P(G)), it can built an input-output system without using a PC.
● 2 types of power supply (AC adapter is an option)
● Various options (DIN-rail mounting plate. Magnets etc.)
Specification
Model | LA-5R | LA-5R(G) |
---|---|---|
Output | 5 Relay (1a) contacts | |
Rated control voltage | AC250V / DC30V (when 5A) ,DC110V (when 0.3A) | |
Limit of load current | Up to 5A per 1 contact (Resistance load) Up to 20A for 5 contacts all (Resistance load)*1 |
|
Minimum applicable load | DC5V, 10mA | |
Relay lifetime | Electric lifetime: More than 50 thousands times (Resistance load is AC250V,5A. When the open/close interval is 30 times per minute)Mechanical lifetime: More than 10 million times(When the open/close interval is 300 times per minute) |
|
Detachable I/O teminal | European terminal 5.08mm pitch, 10 terminals | |
Applicable wire*1 | Single wire φ 2.06 -φ 0.51mm (AWG24 - 12) Stranded wire 3.31 - 0.21mm2 (AWG24 - 12) Peeled length of the coating: 5mm |
|
Torque | 0.5 to 0.6 Nm | |
I/O status display | Output : 5 red LED Power : 1 green LED |
|
Input signal extension | Function to transmit the input state of LA-5P-P, LA-5P-P(G), LA-7P-P(G), or LA-7P-A(G) to this unit. | |
Automatic ON/OFF control | The ON/OFF of the output terminal can be repeated autonomously at the specified cycle (selected from 100msec to 14000msec). | |
Power supply I/O | Supplied from outside | |
LAN interface | RJ45 connector 10Base-T/100Base-TX auto-sensing. Ethernet: IEEE 802.3 | |
LAN protocol*2 | TCP/IP, UDP/IP, ARP, ICMP, SNMP, Telnet, DHCP, BOOTP, HTTP, SMTP | |
LAN state display | RJ45 connector LED: Indicates LAN connection status (on communication, idle, full duplex, half duplex), panel PWR LED*4 | |
Port number*5 | TCP, 10003*6, 30718*7 | |
TCP simultaneous connection | 1 | 4 |
ID setting | No.0 to 15 (16 positions, can be selected by the rotary switch.) | |
Power | DC8 to 30V Non-polar, Maximum 3W 2 inputs, DC-IN1 (AC adapter jack) or DC-IN2 (pin header type 2-pin connector)*9 |
|
Temperature and humidity conditions | Operating temperature: -20 to 55℃ Storage temperature: -25 to 75℃ Humidity: 10 to 95% RH (no condensation) |
|
Atmosphere | No flammable or corrosive gas. There should be no excessive dust (especially conductive dust) | |
Noise resistance | ±1500Vp-p, pulse width 50nS/1µS, normal/common mode. Checked by the noise simulator | |
Withstand voltage | AC2000V for 1 minute Between relay output batch and chassis, between relay output batch and power supply batch |
|
Insulation resistance | 50 MΩ or more at 500 VDC megger, between all inputs and chassis, and between all inputs and all power supplies | Conformed standard | RoHS10 |
Dimensions/&Weight | 74x106x30mm(WxDxH), about 280g | |
Mounting | Just be put on the site or can be fixed using the M3 screw holes on the back of the main unit. Can be mounted on a 35mm DIN rail using the separately sold DIN mounting plate (SI-DIN70/SI-DIN30) |
|
Accessories | Utility & sample software CD, power cable, instruction manual, warranty card |
*1 When a load is connected to all 5 output points, use within 4A per unit.
*2Use bar terminals for stranded wires.
*3 User applications cannot use protocols other than TCP/IP and UDP/IP.
*4 For the (G) version you can check the TCP connection status by change of the color of the PWR LED.
*5 If access to the relevant TCP/UDP port is blocked by a software firewall, etc. due to security policies, etc., change the settings to allow communication. Similarly, when relaying through a router device, etc., allow communication on the corresponding TCP/UDP port.
*6 It can be changed to any port number other than WELL KNOWN PORT NUMBERS.
*7 This is not necessary when connecting directly by IP address without searching for LANIO units.
*8 DC-IN2 is compatible with the attached power cable or the separately sold power branch cable. When making your own cable, use wires of AWG#24 to 22 size, J.S.T. Mfg. Co., Ltd. housing (XHP-2) and crimp contacts (SXH-001T-PO.6).